5 Troubleshooting by event log
5.12 13 xxxx
Continued
Recommended actions
Check that DSF sensors are working.
134325, Move Cartridge failed.
Description
Unknown cartridge position specified: arg
134326, Move Cartridge failed.
Description
Unknown cartridge specified: arg
134327, Move Cartridge failed.
Description
Timeout while waiting for sensor feedback. Cartridge: arg
Position: arg
Recommended actions
Check that cartridge sensors are working.
134329, Get cartridge position failed.
Description
Unknown cartridge specified: arg
134330, Restore cartridge positions failed.
Description
Failed to move cartridges to previously known positions.
Recommended actions
Move cartridges manually back to suitable locations.
134340, VB configuration error.
Description
Maximum catridge volume not specified.
Consequences
System will not behave correctly. Cartridges may not be filled.
Recommended actions
Add the missing value into the VB configuration file.
134341, VB configuration error.
Description
Swap cartridge volume not specified.
Consequences
System will not behave optimally. Cartridges will run completely
empty before swapping occurs.
Continues on next page
574
Recommended actions
Add the missing value into the VB configuration file.
134342, VB configuration error.
Description
Enough catridge volume not specified.
Consequences
System will not behave optimally. Filling will always occur, even
if cartridges have enough volume.
Recommended actions
Add the missing value into the VB configuration file.
134343, VB configuration error.
Description
Split volume not specified.
Consequences
System will not behave optimally. Last cartridge may delay
material change.
Recommended actions
Add the missing value into the VB configuration file.
134350, Move cartridge to home failed.
Description
Operation failed in state: arg
134351, Move cartridge to DSD failed.
Description
Operation failed in state: arg
134352, Move cartridge to DSF failed.
Description
Operation failed in state: arg
134353, Move DSF to cartridge failed.
Description
Operation failed in state: arg
134360, VB maintenance operation error.
Description
Unknown maintenance operation specified: arg