Advertisement

5 Troubleshooting by event log
5.8 7 xxxx
Continued
Recommended actions
Check the Communication configuration.
71116, Not allowed to deactivate I/O device
Description
The I/O configuration of I/O device arg is invalid.
I/O devices with a Device Trust Level containing the parameter
Deny Deactivate is not allowed to be deactivated.
Consequences
This I/O device has been rejected, and no functions depending
on it will work.
Recommended actions
Correct the configuration of the I/O device by either activating
it or changing the Device Trust Level.
71122, Incorrect IP address
Description
The address arg in protocol arg is not a correct IP address.
Recommended actions
Correct the address.
71123, No transmission protocol
Description
The transmission protocol arg given for application protocol
arg could not be found.
Recommended actions
Change the transmission protocol.
71125, Mount permission denied
Description
Permission was denied to mount the directory arg on the server
arg.
Recommended actions
Change the User or Group ID.
71126, Directory not exported
Description
Mounting directory arg as arg failed since it is not exported on
the server computer arg.
Protocol: arg.
Recommended actions
Export the directory on the server computer.
Continues on next page
370
71128, Ethernet not installed
Description
The Ethernet Services option has to be installed when using
remote mounted disk.
Recommended actions
Restart the controller and install the Ethernet Services option.
71129, Too many remote disks
Description
The maximum number of remote mounted disks have been
exceeded.
The maximum number is arg.
Recommended actions
Reduce the number of remote mounted disks.
71130, Too many remote servers
Description
The maximum number of servers for remote mounted disks
has been exceeded.
The maximum number is arg.
Recommended actions
Reduce the number of servers.
71131, Could not mount directory
Description
Mounting directory arg on the computer arg failed.
Protocol: arg.
Recommended actions
Check the server setup.
71141, Default value for I/O signal out of range
Description
The I/O configuration for I/O signal arg is invalid.
The default value is out of range.
This I/O signal has been rejected.
Recommended actions
Change the default value for the I/O signal.
71156, IPC queue full
Description
The inter-process communication (IPC) queue arg was full,
when sending to trap routine.
© Copyright 2005-2018 ABB. All rights reserved.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA