ABB IRC5 Operating Manual page 387

Troubleshooting
Hide thumbs Also See for IRC5:
Table of Contents

Advertisement

Consequences
No communication on the EtherNet/IP is possible. There may
be consequential errors from configuring EtherNet/IP when no
such option has been installed.
Probable causes
An attempt may have been made to add the EtherNet/IP
functionality, without installing the option correctly.
Recommended actions
If the EtherNet/IP option is required: configure a new system
with this option, and install the system. If the EtherNet/IP option
is not required: configure a new system without this option, and
install the system.
71452, Too many EtherNet/IP networks are
configured
Description
Too many EtherNet/IP Industrial Networks are configured. There
is only possibly to have one network for the EtherNet/IP
Scanner/Adapter option.
Recommended actions
Remove one of the EtherNet/IP Industrial Networks from the
I/O configuration. Restart the controller.
71453, Wrong identity for EtherNet/IP adapter
Description
The identity for the adapter arg in the I/O configuration is not
correct.
The correct identity is:
Vendor ID arg.
Device Type arg.
Product Code arg.
Consequences
No contact will be established with this adapter.
Recommended actions
Correct the I/O configuration for the adapter with the identity
information above.
71454, The arg address is missing
Description
No IP address is specified for the arg network.
Consequences
No communication on the arg network is possible.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA
Recommended actions
Specify a valid IP address in the network configuration. Restart
the controller.
71455, EtherNet/IP connection type unknown
Description
The I/O configuration is invalid.
The unit type arg has an invalid/unknown connection type arg.
The connection type must be one of the following: MULTICAST
POINT2POINT
Consequences
This unit type has been rejected.
Recommended actions
Correct the connection type of the unit type. Restart the
controller.
71457, The EtherNet/IP gateway address is invalid
Description
It is not possible to have the gateway address same as the IP
address.
Or the gateway address cannot be same as the default
destination 0.0.0.0.
Consequences
The default controller gateway address arg will be used and
not the specified gateway address arg.
Recommended actions
If no physical gateway is used, do not specify any gateway
address in the configuration. Restart the controller.
71458, Could not change the default gateway
address
Description
If no destination address is specified in the Ethernet/IP
configuration, the default controller gateway address will be
changed. The destination address was not given and the
specified gateway address arg was not valid and could not be
used.
Consequences
No communication on the EtherNet/IP network is possible.
Recommended actions
Correct the gateway in the EtherNet/IP network configuration.
Restart the controller.