ABB IRC5 Operating Manual page 549

Troubleshooting
Hide thumbs Also See for IRC5:
Table of Contents

Advertisement

device has reached the maximum output.
Recommended actions
1. Check if the commanded value to the
regulator is higher than possible for
the application equipment.
2. Reduce setpoint to operate regulator
within controllable range.
133222, arg:Min output
Description
The closed loop regulator for named
device has reached the minimum output.
Recommended actions
1. Check if the commanded value to the
regulator is lower than possible for
the application equipment.
2. Increase setpoint to operate
regulator within controllable range.
133223, arg:Interlock
Description
IPS has discovered an interlock
conflict error. An attempt was made to
operate more than one valve or device
in an interlocked group.
Recommended actions
1. Set active valve or device to zero
before activating a new one.
133224, Acknowledge needed
Description
arg is currently halted by
an alarm supervision and an acknowledge
of named device is needed.
Recommended actions
1. Check the alarms that is halting
the named device.
2. Recover the alarm situation.
3. Acknowledge the alarm for named
device and retry.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA
133225, DMC error
Description
Following Digital Motor Controller (DMC) error message was
sent to IPS:
arg.
IPS has lost communication or discovered an error sent from
the named DMC driver.
Recommended actions
1. Check cables to the DMC.
2. Check power supply to the DMC.
3. For more info, see the Unit Description, Paint manual.
133226, arg.
Description
Setpoint error.
IPS has discovered an error
to set a signal on the named device.
Recommended actions
1. Check if signal is available for
named device.
133250, arg:Comm. err
Description
IPS has discovered an internal
CAN-communication error. Communication
on CAN-bus between IPS nodes is lost.
System will try to reconnect if
possible.
Recommended actions
1. Check CAN-bus cables for IPS nodes.
2. Check IPS nodes for correct MacID.
3. Check CAN-bus termination resistors.
133251, arg:New curve
Description
IPS has created a new dynamic or
calibrated curve, number arg, for
named device.
Recommended actions
133252, arg:Calc. curve
Description
IPS has recalculated a dynamic or
calibrated curve, number arg, for named
© Copyright 2005-2018 ABB. All rights reserved.
5 Troubleshooting by event log
Continues on next page
5.12 13 xxxx
Continued
549