5 Troubleshooting by event log
5.8 7 xxxx
Continued
71264, Conveyor tracking error
Description
Conveyor tracker 'arg' reported error message: arg.
71273, I/O device configuration mismatch
Description
I/O device arg with address arg is configured in the I/O
configuration, but it cannot be found in the network specific
configuration.
Probable causes
The address of the I/O device in the I/O configuration is not the
same as in the network specific configuration. The I/O device
has not been configured at all in the network specific
configuration.
Recommended actions
Check I/O device configuration in the I/O configuration Check
network specific configuration.
71276, Communication established with I/O
device
Description
Communication established with I/O device arg with address
arg on network arg.
71278, Mount permission denied
Description
Permission was denied to mount the directory arg on the server
arg.
Recommended actions
Check the username and password.
71288, Mount path is too large
Description
Mount path is too large. Mount path consists of FTP server
mount point and server path. Max length: arg. Protocol used:
arg.
Recommended actions
Change FTP server mount point or server path.
Continues on next page
374
71289, Memory partition is too big
Description
The memory partition for communication purposes cannot be
allocated. The requested partition arg kB. System partition will
be used.
Recommended actions
Decrease commPartSize.
71290, Could not add FTP device
Description
Adding the FTP device arg to the operating system failed.
Application protocol arg.
Recommended actions
Change the local path of the configuration of the FTP device.
71291, Invalid local path
Description
Local path of the FTP device arg is invalid.
Recommended actions
Local path must end with :
71293, Invalid input size
Description
On DeviceNet I/O device arg the connection input size does
not match the I/O device.
Recommended actions
Change size in I/O configuration. Check module. Use
DN_Generic device template.
71294, Invalid output size
Description
On DeviceNet I/O device arg the connection output size does
not match the I/O device.
Recommended actions
Change size in I/O configuration. Check module. Use
DN_Generic device template.
71295, Invalid input size
Description
On DeviceNet I/O device arg the connection 2 input size does
not match the I/O device.
Recommended actions
Change size in I/O configuration. Check module.
© Copyright 2005-2018 ABB. All rights reserved.
Operating manual - Troubleshooting IRC5