5 Troubleshooting by event log

5.8 7 xxxx

5.8 7 xxxx
71001, Duplicate address
Description
The I/O configuration is invalid.
The same addresses have been given for I/O device arg and
I/O device arg.
I/O devices connected to the same network must have unique
addresses.
This I/O device has been rejected.
Recommended actions
Check that addresses are correct. Check that the I/O devices
are connected to the correct network.
71003, I/O device undefined
Description
The I/O configuration for I/O signal arg is invalid.
Consequences
This I/O signal has been rejected, and no functions depending
on it will work.
Probable causes
The I/O device arg is unknown. All I/O signals must refer to an
existing/defined I/O device.
Recommended actions
Make sure the I/O device is defined. Make sure the I/O device
name is correctly spelled.
71005, Invalid filter time
Description
The I/O configuration for I/O signal arg is invalid.
The passive filter time should either be 0 ms or in the range
[arg, arg] ms.
This I/O signal has been rejected.
Recommended actions
Correct the passive filter time for the I/O signal.
71006, Invalid filter time
Description
The I/O configuration for I/O signal arg is invalid.
The active filter time should either be 0 ms or in the range [arg,
arg] ms.
This I/O signal has been rejected.
Continues on next page
366
Recommended actions
Correct the active filter time for the I/O signal.
71007, Logical values out of range
Description
The I/O configuration for I/O signal arg is invalid.
The logical minimum value must be less than the logical
maximum value.
This I/O signal has been rejected.
Recommended actions
Correct the logical values for the I/O signal so that the minimum
value becomes less than the maximum value.
71008, Physical values out of range
Description
The I/O configuration for I/O signal arg is invalid.
The physical minimum value must be less than the physical
maximum value.
This I/O signal has been rejected.
Recommended actions
Correct the physical values for the I/O signal so that the
minimum value becomes less than the maximum value.
71017, Cross connection without actor I/O signal
Description
The I/O configuration of cross connection arg is invalid.
The parameter Actor arg have been omitted.
Rules: All cross connections must specify at least one actor
signal, i.e. parameter Actor I/O signal 1 must always be
specified. For each operator specified an actor I/O signal must
follow, e.g. if parameter Operator 2 is specified then parameter
Actor 3 must also be specified.
Consequences
The cross connection has been rejected, and no functions
depending on it will work.
Recommended actions
Correct the cross connection so the required actor I/O signal
is specified.