Advertisement

5 Troubleshooting by event log
5.8 7 xxxx
Continued
Probable causes
The submodule in subslot arg in slot arg on device arg cannot
be accessed.
Recommended actions
Check if submodule is defined as a shared device within a
project of another controller. Check diagnostic information of
the I/O device for additional details.
71583, Submodule is locked by another IO
controller
Description
The submodule in subslot arg in slot arg on device arg is locked
by another IO controller.
Consequences
Some I/O signals might not be possible to use.
Probable causes
The submodule in subslot arg in slot arg on device arg cannot
be accessed.
Recommended actions
Check if submodule is defined as a shared device within a
project of another controller. Check diagnostic information of
the I/O device for additional details.
71584, Submodule is locked by another IO
supervisor
Description
The submodule in subslot arg in slot arg on device arg is locked
by another I/O supervisor.
Consequences
Some I/O signals might not be possible to use.
Probable causes
The submodule in subslot arg in slot arg on device arg cannot
be accessed.
Recommended actions
Verify that device is not defined within an I/O Project of another
controller. Check diagnostic information of the I/O device for
additional details.
71585, Submodule is of wrong type
Description
The submodule in subslot arg in slot arg on device arg is of
wrong type.
Consequences
Some I/O signals might not be possible to use.
Continues on next page
402
Probable causes
The submodule in subslot arg in slot arg on device arg is of
wrong type.
Recommended actions
Update the PROFINET configuration file to match the hardware.
Check the I/O device.
71586, Submodule is missing
Description
The submodule in subslot arg in slot arg on device arg is
missing.
Consequences
Some I/O signals might not be possible to use.
Probable causes
The submodule in subslot arg in slot arg on device arg is
missing.
Recommended actions
Update the PROFINET configuration file to match the hardware.
Check the I/O device.
71587, Device command syntax error
Description
Could not send device command to I/O device arg because
there is a syntax error in the command path string.
Device command name arg.
The syntax error: Unsupported segment.
Consequences
The device command was not sent.
Recommended actions
Correct the device command path string.
71588, Device command syntax error
Description
Could not send device command to I/O device arg because
there is a syntax error in the command path string.
Device command name arg.
The syntax error: Duplicated segment.
Consequences
The device command was not sent.
Recommended actions
Correct the device command path string.
© Copyright 2005-2018 ABB. All rights reserved.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA