Consequences
The SID file has not been loaded into power source memory.
Probable causes
The SID file was saved from a different power source type or
the SID file has become corrupted.
Recommended actions
If the file has been transfered with FTP program. Are you sure
that the FTP program uses binary transfer mode for this SID
file?
If possible, try to recreate the SID file from the origin.
112403, Default I/O unit not defined
Description
Task: arg
The default I/O unit is not defined in configuration.
InstancePath: /PROC/ARISTOMIG_INT_USER_PROP/arg
Attribute: use_default_io
112404, Configuration data not found
Description
Task:arg
InstancePath: arg
Attribute: arg
112405, SID file corrupt
Description
Task:arg
Context: arg
The SID file is not in the correct format or the file size is
incorrect.
Consequences
All the data was not recovered from the file.
Recommended actions
Verify the schedules in the power source. All data might not be
recovered.
112406, Invalid tuning parameter
Description
Task:arg
Context: arg
arg is not a valid tuning parameter in instance arg.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA
112407, Schedule does not exist
Description
The schedule arg does not exist in the power source arg, in
arg.
Consequences
The welding results will not be as expected.
Recommended actions
Make sure that the schedule has been created before using it
in a weld instruction.
112410, Program memory error (EPROM)
Description
The program memory is damaged in unit arg.
Fault code: arg
Internal unit: arg
Recommended actions
Restart the machine. If the fault persists, send for a service
technician.
112411, Microprocessor RAM error
Description
The microprocessor is unable to print/read to the internal
memory in unit arg.
Fault code: arg
Internal unit: arg
Recommended actions
Restart the machine. If the fault persists, send for a service
technician.
112412, External RAM error
Description
The microprocessor is unable to print/read to the external
memory in unit arg.
Fault code: arg
Internal unit: arg
Recommended actions
Restart the machine. If the fault persists, send for a service
technician.
112413, 5V power supply low
Description
The power supply voltage is too low in unit arg.
Fault code: arg
© Copyright 2005-2018 ABB. All rights reserved.
5 Troubleshooting by event log
Continues on next page