39426, Rectifier internal failure
Description
The rectifier on communication link arg attached to drive module
arg has detected an internal failure.
Consequences
No operation will be possible until after correcting the fault. The
system goes to status SYS HALT.
Probable causes
This may be caused by a faulty or lacking signal connection
between the rectifier and drive units.
Recommended actions
Make sure the signal cable is correctly connected between the
rectifier and drive unit. Check the indication LEDs on the rectifier
and drive units. The significance of the LEDs is described in
the Trouble Shooting Manual.
39427, Rectifier communication missing
Description
The communication with the rectifier on drive communication
link arg, drive module arg has been lost.
Consequences
No operation will be possible until after correcting the fault. The
system goes to status SYS HALT.
Probable causes
This may be caused by a faulty or lacking signal connection
between the rectifier and drive units.
Recommended actions
Make sure the signal cable is correctly connected between the
rectifier and drive unit. Perform a shutdown and then restart
the controller. If the problem persists, isolate the faulty unit and
replace it.
39428, Rectifier startup error
Description
The rectifier on drive communication link arg, drive module arg
has detected a startup error.
Consequences
No operation will be possible until after correcting the fault. The
system goes to status SYS HALT.
Probable causes
This may be caused by an internal error in the rectifier unit.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA
Recommended actions
Make sure the signal cable is correctly connected between the
rectifier and drive unit. Perform a shutdown and then restart
the controller. If the problem persists, isolate the faulty rectifier
unit and replace it.
39431, Update of Drive Unit Software in Progress
Description
The drive unit software in drive module arg is being updated.
Please wait for the upgrade to be completed. This will take
approximately 3.5 minutes.
NOTE: Please do not turn off the power or restart the controller
until the download is complete.
Recommended actions
Please wait...
39432, Incompatible boot version in drive unit
Description
The boot version in drive module arg is version arg, which is
not allowed. The latest allowed boot version is arg.
Consequences
No operation will be possible until after correcting the fault. The
system goes to status SYS HALT.
Probable causes
The boot version is not compatible with the hardware version.
Recommended actions
Replace the drive unit with one using a boot version equal to
or greater than the latest allowed one.
39434, Drive Unit Start Failure
Description
The drive unit in drive module arg failed to start. drive boot
status = arg. drive dsp1 status = arg.
Consequences
The robot cannot be operated.
Probable causes
A number of errors may cause this.
Recommended actions
Switch the main power off to the module and then switch it back
on. Note that a normal restart will NOT suffice! If the problem
persists, replace the drive unit.