5 Troubleshooting by event log
5.8 7 xxxx
Continued
71459, Illegal address for EtherNet/IP
Description
The address arg for the EtherNet/IP network is illegal.
Consequences
No communication on the EtherNet/IP network is possible.
Recommended actions
Correct the address in the EtherNet/IP network configuration.
Restart the controller.
71460, Not able to connect to EtherNet/IP adapter
Description
The configured adapter arg with address arg does not physically
exist on the EtherNet/IP network.
Consequences
It is not possible to access the adapter itself or I/O signals on
the adapter since it is currently not communicating with the
controller.
Probable causes
The adapter does not exist physically.
The adapter address is wrong.
The adapter is malfunctioning.
Recommended actions
Check that the adapter physically exists on the EtherNet/IP
network and that the address is correct. If the address has been
changed, restart the controller.
71461, Duplicated address on the EtherNet/IP
network
Description
The adapter arg and the EtherNet/IP scanner have been
configured with the same address in the controller.
Consequences
It is not possible to access the adapter or I/O signals on it, since
it is currently not communicating with the controller.
Recommended actions
Change the address for the adapter arg or the address for the
EtherNet/IP controller in the I/O configuration. If changing the
I/O device address and it have this address physically it must
also be changed in the adapter.Restart the controller.
71462, Illegal subnet mask for EtherNet/IP
Description
The subnet mask arg for the EtherNet/IP network is illegal.
Continues on next page
388
Consequences
No communication on the EtherNet/IP network is possible.
Recommended actions
Correct the subnet mask in the EtherNet/IP network
configuration. Restart the controller.
71463, Illegal address for EtherNet/IP network
Description
The EtherNet/IP address arg is reserved.
Consequences
No communication on the EtherNet/IP network is possible.
Probable causes
The specified address is on a subnet reserved by another
Ethernet port. Two Ethernet ports on the controller cannot be
on the same subnet.
Example:
EtherNet/IP port: 192.168.125.x
Service port: 192.168.125.x
Note:
The subnets within the range 192.168.125.xxx - 192.168.130.xxx
are predefined and cannot be used.
Recommended actions
Change the address to another subnet. Restart the controller.
71464, Could not add a new gateway for
EtherNet/IP
Description
Could not add the gateway address arg with the destination
address arg for EtherNet/IP.
Consequences
No communication on the EtherNet/IP network is possible.
Probable causes
The gateway address or the destination address are invalid.
No destination address have been specified.
Recommended actions
Correct the gateway address or the destination address in the
EtherNet/IP network configuration. Restart the controller.
71469, Max number of internal I/O signals
exceeded
Description
The I/O configuration is invalid.
The maximum number, arg, of internal I/O signals in the I/O
system has been exceeded.