5 Troubleshooting by event log
5.6 4 xxxx
Continued
41848, Too low visualization time
Description
Task: arg.
The specified visualization time is too low.
Program ref: arg.
Consequences
The program execution is stopped immediately.
Recommended actions
Check the RAPID documentation regarding the minimum
visualization time. Increase the visualization time used in the
RAPID program.
41849, Bad combination of values used in
arguments
Description
Task: arg.
The specified visualization time arg is equal or higher than the
timeout arg for the instruction.
Program ref: arg.
Consequences
The program execution is stopped immediately.
Recommended actions
Change the visualization time used in the RAPID program, or
change the maximum period of waiting time permitted.
41850, User interface already active
Description
Task: arg.
A message is already active on the FlexPendant. A message
launched by instruction arg must be aborted before launching
a new message.
Program ref: arg.
Consequences
The message will not be presented on the FlexPendant. This
error can be handled in an error handler.
Probable causes
A arg message is already active on the FlexPendant.
Recommended actions
Recovery: arg. The current active arg message can be
deactivated with instruction arg.
Continues on next page
318
41851, Wrong value type used
Description
Task: arg.
Wrong value type used in optional argument arg. The only valid
types are bool, num or dnum, or any alias type of those three
base types.
Program ref: arg.
Consequences
The program execution is stopped immediately.
Probable causes
Wrong value type used.
Recommended actions
Change type used in optional argument arg.
41852, Wrong signal value for signal arg
Description
It is not possible to set the I/O signal arg to value arg.
Consequences
The program execution is stopped immediately.
Probable causes
The I/O signal arg is configured wrong, or the value that should
be set is wrong. The signal value that is used has been read
from a persistent variable specified in one of the setup
instructions used for Trigg defining conditions and actions for
setting a digital, a group of digital, or an analog output signal
at a fixed position. The error is detected when the actual signal
setting should be done.
Recommended actions
Check the I/O configuration for I/O signal. Check the value of
the persistent variable that is used in arg for the setup
instruction(s) for Trigg.
41860, Evaluation error in Cyclic bool
Description
Failure while evaluating the Cyclic bool arg.
Consequences
The evaluation of arg has been stopped immediately.
Probable causes
The module containing the declaration of arg has been
unloaded. An I/O signal needed to evaluate the logical
expression connected to arg has been lost (see earlier error
logs). The I/O signal that is updated with the cyclic bool value
has been lost.