24.5.3 Switch setting of CC-Link
module (Q Series)
Set the station number setting switch, transmission speed /
mode setting switch.
QJ61BT11,QJ61BT11N
(1) Station number setting switch
Station number
Description
setting switch
Station number
setting (master
station)
: Necessary
(2) Transmission rate/mode setting switch
Transmission
rate/mode
Description
setting switch
Transmission rate/
mode setting
: Necessary
POINT
POINT
POINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
(1)
(2)
Setting necessity
Set value
at GOT connection
0 (fixed)
: As necessary
: Not necessary
Setting necessity
Set value
at GOT connection
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
: As necessary
: Not necessary
24.5.4 [Network parameter] of GX
Developer
(1) Network parameter
Item
No. of boards in module
Start I/O No.
Operational setting
(Use default value)
Type
Master station (fixed)
Mode
Remote net (Ver.1 mode)
All connect count
Remote input (RX)
Remote output (RY)
Remote register (RWr)
Remote register (RWw)
Special relay (SB)
Special register (SW)
Retry count
Automatic reconnection
station count
Stand by master station No.
(Use default value)
PLC down select
Scan mode setting
Delay information setting
Station information setting
Remote device station initial
setting
(Use default value)
Interrupt setting
: Necessary
24. CC-Link CONNECTION (Via G4)
24.5 PLC Side Setting
Setting necessity
Set value
at GOT
connection
1
0000
H
1
X400
Y400
D300
D200
SB0
SW0
Refer to (2).
: As necessary
: Not necessary
24 - 13