Avaya S8700 Maintenance Manual page 95

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Fault Isolation for Fiber Links
3. Enter list fiber-link to get the physical location of the fiber link's endpoints.
If a DS1 CONV is administered to the fiber link (DS1 CONV is "y"), use the
display fiber-link command to get the physical location of the DS1 CONV
circuit packs on the fiber link.
4. Execute busyout fiber-link FP, followed by test fiber-link FP long.
If any tests in the sequence fail, proceed with
If every test passes, clear alarms by executing test board UUCSS long
clear for every alarmed EXP-INTF circuit pack. Wait 5 minutes for any
SNI-BD, SNI-PEER, FIBER-LK, or DS1C-BD alarms to clear. You can
speed this process with clear firmware counters [a-pnc | b-pnc] for the
PNC that was repaired. You are finished with this procedure.
5. For each of the fiber link's endpoints, follow this flowchart:
555-233-143
If there are many SNI-PEER errors with the same error type, replace
the indicted SNI circuit pack using the following table.
Error Type
SNI's Slot
1
2
257
3
513
4
769
5
1025
6
1281
7
1537
8
1793
9
2049
13
2305
14
2561
15
2817
16
3073
17
3329
18
3585
19
3841
20
After replacing an SNI circuit pack, clear alarms by executing test
board UUCSSlong clear for every alarmed EXP-INTF circuit pack.
Wait 5 minutes for any SNI-BD or SNI-PEER alarms to clear. To
speed this process use clear firmware counters [a-pnc | b-pnc]
for the PNC that was repaired.
Exit this procedure.
step
5.
Issue 1 May 2002
4-21