Figure 16-5 Crimping Tool; Figure 16-6 Terminal Connector Crimped To The Power Cable - Cisco ONS 15310-MA SDH Procedure Manual

Hide thumbs Also See for ONS 15310-MA SDH:
Table of Contents

Advertisement

Figure 16-5
Locator
Terminal
Close the tool until the ratchet releases.
Step 8
Figure 16-6
Figure 16-6
Step 9
Carefully remove the crimped terminal.
Step 10
Insert crimped terminal into outside holes of the supplied 3-pin receptacle. Leave the center hole empty.
The D-shaped terminal is for BAT (–48V). The O-shaped terminal on the other side of the connector is
for RET.
Note
Note
Plug the DC power connector into either plug on the rear of the chassis at the outside corners of the
Step 11
ONS 15310-MA SDH.
Cisco ONS 15310-MA SDH Procedure Guide, Release 9.1 and Release 9.2
16-8
Crimping Tool
shows the terminal crimped to the power cable.
Terminal Connector Crimped to the Power Cable
Insulation crimp
This power cable is suitable for maximum 5A, 60 VDC.
The DC power Battery Return (BR) or positive terminal, must be grounded at the source end
(power feed or DC mains power end). The DC power BR input terminal of the ONS 15xxx is not
connected to the equipment frame (chassis).
Chapter 16
Conductor
grips
Insulation
grips
Wire
DLPs H1 to H99
78-19416-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents