Permissible Line Supplies Dependent On The Installation Altitude - Siemens SINUMERIK 808D ADVANCED Series Commissioning Manual

Hide thumbs Also See for SINUMERIK 808D ADVANCED Series:
Table of Contents

Advertisement

Frame size
Shock
Vibration
Certification
Outline dimensions (W × H × D, mm)
Net weight
The values here are given at rated load.
1)
The overvoltage threshold is 820 VDC; the undervoltage threshold is 320 VDC.
2)
15.2.3

Permissible line supplies dependent on the installation altitude

● For installation altitudes ≤ 2000 m above sea level, it is permissible to connect the V70 drive to any of the line supplies
that are specified for it.
● For installation altitudes 2000 m to 5000 m above sea level, you must connect a V70 drive to any of the specified line
supplies either via an isolating transformer or with a grounded neutral point.
Commissioning Manual
6FC5397-4EP10-0BA8, 07/2018
FSB
Operation
Operational area: II
Ambient classification: 3M2
Peak acceleration: 5 g + 15 g
Duration: 30 ms + 11 ms
Quantity of shocks: 3
Summed shocks: 18
Cycle time: 1 s
Transport &
Covered by vibration test
storage
Operation
Operational area II/3M2
10 Hz to 58 Hz: 0.075 mm deflection
58 Hz to 200 Hz: 1g vibration
Transport &
5 Hz to 9 Hz: 3.5 mm deflection
storage
9 Hz to 200 Hz: 1 g vibration
Ambient Classification: 1M2
100 × 180
× 220
2.35 kg
FSC
140 × 260 × 240
5.05 kg
FSD
190 × 350 × 185
8.05 kg
8.3 kg