33.2.10 GOT side settings

Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the
GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: OMRON
• Controller Type: Set according to the Controller
Type to be connected.
• OMRON SYSMAC
• OMRON SYSMAC CS/CJ
• I/F: Interface to be used
• Driver: OMRON SYSMAC
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
33.2.10  Communication detail settings
OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
33 - 28
33. CONNECTION TO OMRON PLC
33.2 Serial Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
Item
Transmission Speed
3.
Data Bit
4.
Stop Bit
Parity
Retry
Timeout Time
Host Address
Delay Time
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Set this item when change the
data length used for
communication with the connected
equipment.
(Default: 7bits)
Specify the stop bit length for
communications.
(Default: 2bits)
Specify whether or not to perform
a parity check, and how it is
performed during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address (station
No. of the PLC to which the GOT
is connected) in the network of the
GOT.
(Default: 0)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0ms)
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bit (fixed)
2bit (fixed)
Even (fixed)
0 to 5times
3 to 30sec
0 to 31
0 to 300
(ms)