Connecting To Pc Link Module (F3Lc11-1F, F3Lc12-1F) - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

50.2.9 Connecting to PC link module
(F3LC11-1F, F3LC12-1F)
Switch setting on the PC link module
Set the switches accordingly.
POINT
POINT
POINT
Switch setting
Set the switches before mounting the Ethernet
Interface Module on the base unit.
F3LC11-1F
F3LC12-1F
A
(1) Transmission speed switch (SW1)
Set the same transmission speed of the GOT.
*1
Setting
4
5
7
9
A
C
*1
Only transmission speeds available on the GOT side are
shown.
Side view indicated by A
With right side cover
removed
(1)
A
(2)
(3)
Transmission speed
4800bps
9600bps
19200bps
38400bps
57600bps
115200bps
(2) Data format switch (SW2)
Set the character length, parity, stop bit and checksum
consistent with the corresponding settings on the GOT
side.
Switch No.
1
Character length
2
Parity
3
4
Stop bit
5
Checksum
End character
6
specification
7
Protect function
8
Security function
(3) Module function switch (SW3)
Switch No.
User setting
1 to 6
inhibited
Modem
7
compatibility
8
External modem
50. CONNECTION TO YOKOGAWA PLC
50.2 Serial Connection
Description
Setting
ON (8bits),
OFF (7bits)
ON (done),
OFF (none)
ON (even),
OFF (odd)
ON (2bits),
OFF (1bit)
ON (done),
OFF (none)
OFF (none)
OFF (none)
OFF (none)
Description
Setting
OFF
OFF (not
compatible)
OFF (none)
50 - 17
48
49
50
51
52
53
54
55

Advertisement

Table of Contents
loading

Table of Contents