51.5 Temperature Controller Side Setting

POINT
POINT
POINT
(1) YOKOGAWA temperature controller
For details of YOKOGAWA temperature controller,
refer to the following manual.
User's Manual of the YOKOGAWA temperature
controller
(2) Interface converter
For details on communication settings of the
RS232C/RS485 converter, refer to the following
manual.
User's Manual of RS232C/RS485 converter
Name
Series name/model name
GREEN
UT100
Temperature controller
UT2000
UTAdvanced
Interface converter
ML2-

51.5.1 Connecting to GREEN Series

Communication settings
Make the communication settings by operating the key
of the temperature controller.
(1) For the UT/UP/UM/US100(except UT750, UP750)
Item
Transmission speed
9600bps (fixed)
*1
7bits, 8bits
Data bit
*1
Even, Odd, None
Parity bit
*1
1bit, 2bits
Stop bit
*1*2
1 to 99
Address
0: PC link communication (without sum check)
*1
Protocol selection
1: PC link communication (with sum check)
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
(2) For the UT750, UP750
Item
RS-485 communication 9600bps (fixed)
Transmission
High performance
*1
speed
RS-485 communication
*1
7bits, 8bits
Data bit
*1
Even, Odd, None
Parity bit
*1
1bit, 2bits
Stop bit
*1*2
1 to 99
Address
RS-485 communication
Protocol
*1
selection
High performance
RS-485 communication
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
Refer to
51.5.1
51.5.2
51.5.3
51.5.4
51.5.5
Set value
Set value
9600bps, 19200bps, 38400bps
0: PC link communication (without sum check)
1: PC link communication (with sum check)
0: PC link communication (without sum check)
1: PC link communication (with sum check)
51. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER

51.5.2 Connecting to UT100 Series

Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
Transmission speed
9600bps
*1
7bits, 8bits
Data bit
*1
Even, Odd, None
Parity bit
*1
1bit, 2bits
Stop bit
*1*2
1 to 99
Address
0: PC link communication (without sum check)
*1
Protocol selection
1: PC link communication (with sum check)
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.

51.5.3 Connecting to UT2000 Series

Communication settings
Make the communication settings using setting
switches.
Item
Transmission speed
9600bps
*1
8bits (Fixed)
Data bit
*1
Even, Odd, None
Parity bit
*1
1bit (Fixed)
Stop bit
*1*2
1 to 16
Station No.
Communication mode
PC link communication mode
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
Settings by switch
(1) Settings of the transmission speed and the parity
Make those settings by operating the communication
setting Rotary switch.
Transmission
Switch position
speed
0
1
9600bps
2
51.5 Temperature Controller Side Setting
Set value
Set value
Communication mode
select DIP SW
Communication setting
Rotary switch
Station No. select
Rotary switch
Parity bit
None
Odd
Even
51 - 25
48
49
50
51
52
53
54
55

Advertisement