34.4 GOT Side Settings
34.4.1
Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: OMRON
• Controller Type: OMRON THERMAC/INPANEL
NEO
• I/F: Interface to be used
• Driver: OMRON THERMAC/INPANEL NEO
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
34.4.2 Communication detail settings
OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
34 - 10
34. CONNECTION TO OMRON TEMPERATURE CONTROLLER
34.4 GOT Side Settings
Click!
[Controller Setting] from the
34.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Transmission
Speed
3.
Data Bit
4.
Stop Bit
Parity
Retry
Timeout Time
Delay Time
Format
POINT
POINT
POINT
(1) Delay Time
When connecting to the temperature controller
E5ZN, set the delay time to 5ms or more.
(2) Format setting
The compatible format of temperature controller
differs depending on model.
E5AN, E5CN, E5EN, E5GN
E5ZN
For the continuous access and random access of
the temperature controller, refer to the following
manual.
User's Manual of the OMRON temperature
controller
(3) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(4) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication with the
connected equipment. (Default: 7bits)
Specify the stop bit length for
communications. (Default: 2bits)
Specify whether or not to perform a
parity check, and how it is performed
during communication. (Default: Even)
Set the number of retries to be performed
when a communication error occurs.
(Default: 0time)
Set the time period for a communication
to time out. (Default: 3sec)
Set this item to adjust the transmission
timing of the communication request
from the GOT. (Default: 2ms)
Select the communication format.
(Default: 1)
format 1: only continuous access
format 2: continuous and random access
Model
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
0 to 300 (ms)
1/2
Compatible format
Format 1 only
Format 1 or Format 2