53.5.15 Connecting to X-TIO Module

Communication settings
Make the communication settings of the temperature
controller.
Item
*1
9600bps, 19200bps, 38400bps
Communication speed
Communication protocol 1
MODBUS
Data bit: 8bits, Parity: None
Data bit: 8bits, Parity: Even
Data bit configuration
Data bit: 8bits, Parity: Odd
Stop bit: 1bit (fixed)
*2
1 to 99
Module address
When combining the module, turn ON the
Internal data bus terminating
internal data bus terminating resistor at both
resistor
ends of the module.
Data interval extension time 0 to 99ms
*1
Adjust the settings with GOT settings.
*2
When the setting value is set to 0, a communication is not
made.
Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol
Item
Set value
1
9600bps
ON OFF
Communicati
19200bps
OFF ON
on speed
38400bps
ON
Data bit: 8bits,
Parity: None
Data bit
Data bit: 8bits,
configuration
Parity: Even
Data bit: 8bits,
Parity: Odd
Communicati
MODBUS
on protocol
Internal data
OFF
bus
termination
ON
resistor
setting
Data interval
extension
0 to 99ms
time
Setting range
Dip switch
ON
ON
ON
OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Switch No.
2
3
4
5
6
7
8
ON
ON OFF OFF
ON OFF ON
ON
ON
ON
ON
OFF
ON
ON OFF ON
53. CONNECTION TO RKC TEMPERATURE CONTROLLER
Unit address settings
Set the unit address using the rotary switch (address
setting switch).
Rotary switch
(Address setting switch)
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
Data interval extension time settings
Set the data interval extension time as the following
procedure.
1.
Turn the power of the module OFF.
2.
Set the DIP switch 4 and 6 to "ON" and 5 to "OFF".
3.
Set the data interval extension time using the rotary
switch (address setting switch).
The setting method is the same as that of the module
address.
4.
Turn the power of the module ON.
The FAIL/RUN lamp lights in green and the set time
becomes valid.
5.
Turn the power of the module OFF again and set the
DIP switches and rotary switch to the original position.

53.5.16 Connecting to SB Series

Communication settings
Item
Communication protocol
1: MODBUS
Device address
1 to 99
*1
(Slave address)
2: 9600bps
*2
Communication speed
3: 19200bps
Data bit configuration
Refer to  Data bit configuration.
*3
0 to 250
Interval time
*1
When the setting value is set to 0, a communication is not
made.
*2
Adjust the settings with GOT settings.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
53.5 Temperature Controller Side Setting
Upper digit setting
(Set value x10)
Lower digit setting
(Set value x1)
*1
Setting range
53 - 45
48
49
50
51
52
53
54
55