36.5.7 Connecting to D0-DCM

Communication settings
Write the following communication settings to the
specified register using the programmer. For details of
the register, refer to the following manual.
KOYO EI PLC user's Manual
Item
MODE
HEX
Protocol
DirectNet
Station No.
1 to 90
9600bps, 19200bps, 38400bps,
*1
Transmission speed
57600bps, 115200bps
NONE, ODD,
Parity
EVEN (Only communication port 2)
RTS On Delay Time
0ms
(Only communication port 2)
RTS Off Delay Time
0ms
(Only communication port 2)
Timeout
800ms/960ms/1200ms/1600ms/4000ms/
(Only communication port 2)
8000ms/16000ms/40000ms
485 mode selection
RS232 • RS422/485 4 line type
(Only communication port 2)
Data bit
8bits, 7bits
(Only communication port 2)
Stop bit
1bit, 2bits
(Only communication port 2)
The timeout between
characters
0 to 9999ms
(Only communication port 2)
The completion of a setting
Default use,A preset value is effective
Reset timeout
Invalid,Effective
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Specify the transmission speed to match the transmission
speed of the GOT.
36.5.8 Connecting to D2-DCM
Communication settings
Make the following settings using the programmer.
Item
Station No.
1 to 90
*1
9600bps, 19200bps, 38400bps
Transmission speed
Data bit
8bits (Fixed)
Stop bit
1bit (Fixed)
Parity
NONE, ODD
Self-diagnostic mode
OFF
Response delay time
0ms
Peer to Peer
OFF
Master/Slave
Slave
Timeout
Enable
MODE
HEX
MODBUS
OFF
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Specify the transmission speed to match the transmission
speed of the GOT.
Set value
Set value
36.5.9 Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
Station No.3
GOT
The example of a Station No. setting
(1) Direct specification
Specify the station No. of the PLC to be changed when
setting device.
Specification range
1 to 90
36. CONNECTION TO KOYO EI PLC
36.5 PLC Side Setting
Station No.1
Station No.15
36 - 33
32
33
34
35
36
37
38
39