24.5 PLC Side Setting

Model
Peripheral connection
module
CC-Link module
24.5.1 Connecting AJ65BT-G4-S3
This section describes the settings of the GOT and
peripheral connection module in the following case of the
system configuration.
POINT
POINT
POINT
(1) Peripheral connection module
For details of the peripheral connection module,
refer to the following manual.
Peripheral Connection Module Type AJ65BT-
G4-S3 User's Manual (detail volume)
(2) CC-Link module
For details of the CC-Link module, refer to the
following manual.
CC-Link System Master/Local Module User's
Manual QJ61BT11N
MELSEC-L CC-Link System Master/Local
Module User's Manual
(3) CC-Link function built-in CPU
For details on the CC-Link function built-in CPU,
refer to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
System configuration
24.5.3 Switch setting of CC-Link module (Q Series)
24.5.4 [Network parameter] of GX Developer
<CC-Link module>
Station type
Station No.
Mode
All connect count
Transmission speed
24.5.6 [Controller Setting] of GT Designer3
<AJ65BT-G4-S3>
Station type
Station No.
Number of stations occupied
Transmission speed
 Switch setting of peripheral connection module
*1
The Start I/O No. of the CC-Link module is set to "0"
24 - 10
24. CC-Link CONNECTION (Via G4)
24.5 PLC Side Setting
Reference
AJ65BT-G4-S3
24.5.1
AJ65BT-R2N
24.5.2
QJ61BT11
24.5.3
QJ61BT11N
*1
Setting example
: Master station
: Station No. 0
: Remote net (Ver.1 mode)
: 1
: 156kbps
<GOT>Setting example
Transmission speed: 9600bps
Setting example
: Intelligent device station
: Station No. 1
: Exclusive station 1
: 156kbps
Switch setting of peripheral connection
module
Set the station number setting switch, data link
transmission speed setting switch, and operation setting
DIP switch.
(1) Station number setting switch
Station number setting
Description
switch
AJ65BT-G4-S3
station number
setting
: Necessary
(2) Data link transmission speed setting switch
Data link transmission
Description
speed setting switch
Data link
transmission
speed setting
: Necessary
(2)
(1)
(3)
Setting necessity
Set value
at GOT connection
1 to 64
: As necessary
: Not necessary
Setting necessity
Set value
at GOT connection
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
: As necessary
: Not necessary