Plc Side Setting; Connecting To Ethernet Interface Module (F3Le01-5T, F3Le11-0T) - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

Ethernet setting
Item
Description
The host is displayed. (The host is
Host
indicated with an asterisk (*).)
Set the network No. of the connected
N/W No.
Ethernet module.
(Default: blank)
Set the station No. of the connected
*3
Ethernet module.
PLC No.
(Default: blank)
Controller Type
YOKOGAWA (fixed)
Set the IP address of the connected
*1
Ethernet module.
IP Address
(Default: blank)
Set the port No. of the connected
*2
Ethernet module.
Port No.
(Default: 12289)
Select a communication protocol.
*1
Communication
(Default: UDP)
*1
Set the same IP address and communication format as
those of the PLC side.
*2
Set the port No. of the host link service used on the PLC
side.
*3
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
50.3.2  Communication detail settings
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GT User's Manual
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.

50.3.3 PLC side setting

POINT
POINT
POINT
YOKOGAWA PLC
For details of YOKOGAWA PLCs, refer to the following
manuals.
Set value
Ethernet interface module
-
F3SP66 (built-in Ethernet interface)
F3SP67 (built-in Ethernet interface)
1 to 239
F3SP71-4N (built-in Ethernet interface)
50.3.4 Connecting to Ethernet
1 to 64
YOKOGAWA
(fixed)
PLC side IP
address
Switch settings of Ethernet Interface Module
Set the switches accordingly.
12289, 12291
POINT
POINT
POINT
UDP, TCP
Switch setting
Set the switches before mounting the Ethernet
interface module on the base unit.
(1) IP address switch
Set the IP address with eight Hex rotary switches on
the side of the base unit.
Hexadecimal
Decimal
50. CONNECTION TO YOKOGAWA PLC
YOKOGAWA PLC user's Manual
Model
F3LE01-5T
F3LE11-0T
F3LE12-0T
interface module (F3LE01-5T,
F3LE11-0T)
F3LE01-5T
Condition setting
switch
IP address switch
Right side view without the cover
C0
A8
192
168
50.3 Ethernet Connection
48
49
Refer to
50.3.4
50.3.5
50
50.3.6
51
52
F3LE11-0T
53
54
55
FA
D2
250
210
50 - 23