(3) Setting command level/parity/transmission code
(SW4)
Setting
2
(fixed)
(4) Setting DIP switches
Switch No.
1
2
3
4
(5) Setting the CTS switch
Switch setting on C200H-LK202-V1
Set the switches accordingly.
Front
LK201-V1
RUN
XM
RCV
ERROR
(1)
(1)
SW1
SW2
(2)
(3)
SW4
SW3
(1) Setting station No. (SW1, SW2)
Set the station No. within the range of 00 to 31.
Set the station No. according to the Host Address on
the GOT side.
Rotary
switch
SW1
SW2
Contents of setting
Comman
Transmissi
Parity
d level
on code
Levels 1,
ASCII 7
2 and 3
Even
bits
are
2 stop bits
enabled
Set value
OFF
OFF
ON (1:N procedure)
OFF (no 5V power supply)
Setting
0V
Rear
(5)
(4)
Description
Setting
Station No.
upper digit
0 to 3
1
(×10
)
Station No.
lower digit
0 to 9
0
(×10
)
(2) Setting transmission speed (SW3)
Set the same transmission speed of the GOT.
Setting
4
5
6
*1
Only transmission speeds available on the GOT side are
shown.
(3) Setting command level/parity/transmission code
(SW4)
Setting
2
(fixed)
(4) Setting the 1:1/1:N procedure switch
(5) Setting the terminating resistor connection switch
ON (terminating resistor attached)
33. CONNECTION TO OMRON PLC
33.2 Serial Connection
*1
Set value
4800bps
9600bps
19200bps
Contents of setting
Comman
Transmissi
Parity
d level
on code
Levels 1,
ASCII 7
2 and 3
Even
bits
are
2 stop bits
enabled
Setting
OFF (1:N procedure)
Setting
33 - 33
32
33
34
35
36
37
38
39

Advertisement