Connecting To Z-Com - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

Unit address settings
Set the unit address using the unit address setting
switch.
Module address setting switch
Interval time settings
Configure the interval time setting using the RKC
communication setting tool (WinPCI).
After the communication is started, set as follows.
Setting item
Instrument
CFG file
Interval time
Setting range: 0 to F
Set value
0
ZTIO_rkc.cfg
0 to 250ms
53. CONNECTION TO RKC TEMPERATURE CONTROLLER

53.5.4 Connecting to Z-COM

Communication settings
Item
*1
Communication speed
Communication protocol
Data bit
Parity
Stop bit
*2
Unit address
Interval time
Dip switch settings valid / invalid
*1
Adjust the settings with GOT settings.
*2
Select the unit address without overlapping with that of other
units.
Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol.
COM
COM.
PORT1
COM1
COM.
PORT2
COM.
PORT3
COM1
COM.
PORT4
Front side
Setting item
Set value
1
9600bps
ON OFF
Communicati
on speed
19200bps
OFF ON
(COM1)
38400bps
ON
Communicati
Host
on protocol
(MODBUS)
(COM1)
Communicati
9600bps
on speed
19200bps
(COM2)
Communicati
Host
on protocol
(MODBUS)
(COM2)
Dip switch
settings
Valid
valid/invalid
53.5 Temperature Controller Side Setting
Setting range
9600bps, 19200bps, 38400bps
Host (MODBUS)
8bits (Fixed)
None (fixed)
1bit (Fixed)
0 to F
0 to 250ms
Valid
Dip switch
OFF
Right side
Switch No.
2
3
4
5
6
7
ON
ON
OFF
ON
ON OFF OFF
OFF
53 - 41
48
49
50
51
ON
52
8
53
54
55