48.5 Temperature Controller Side Setting

POINT
POINT
POINT
(1) FUJI temperature controller
For details of FUJI temperature controller, refer to
the following manual.
User's Manual of the FUJI temperature
controller
(2) Interface converter
For details on communication settings of the
RS232C/RS485 converter, refer to the following
manual.
User's manual of interface converter
Model
PXR3, PXR4, PXR5, PXR9
Temperature controller
PXG4, PXG5, PXG9
PXH9
RC-77
SI-30A
Interface converter
KS-485
K3SC-10

48.5.1 Connecting to PXR3/4/5/9

Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
Transmission speed
9600bps (fixed)
Data bit
8bits (Fixed)
*1
Even, Odd, None
Parity bit
Stop bit
1bit (Fixed)
*2
1 to 255
Station No.
Communication protocol
MODBUS
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other units.
Refer to
48.5.1
48.5.2
48.5.3
48.5.4
48.5.5
48.5.6
48.5.7
Set value
48. CONNECTION TO FUJI TEMPERATURE CONTROLLER
48.5.2

Connecting to PXG4/5/9

Communication settings
Make the communication settings by operating the key
of the temperature controller.
(1) RS-485 communication settings
Item
*1
9600bps, 19200bps
Transmission speed
Data bit
8bits (Fixed)
*1
Even, Odd, None
Parity bit
*1
1bit (Fixed)
Stop bit
*2
1 to 255
Station No.
Communication
Read only permission or read and overwrite
*3
permission
permissions
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other units.
*3
Set as necessary.
(2) RS-232 communication settings (PC loader
communication)
Item
Transmission speed
9600bps (fixed)
Data bit
8bits (Fixed)
Parity bit
None (fixed)
Stop bit
1bit (Fixed)

48.5.3 Connecting to PXH9

Communication settings
Make the communication settings by operating the key
of the temperature controller.
(1) RS-485 communication settings
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
Data bit
8bits (Fixed)
*1
Even, Odd, None
Parity bit
Stop bit
1bit (Fixed)
*2
1 to 255
Station No.
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other units.
(2) RS-232 communication settings (PC loader
communication)
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
Data bit
8bits (Fixed)
*1
Even, Odd, None
Parity bit
Stop bit
1bit (Fixed)
Station No.
1 (fixed)
*1
Adjust the settings with GOT settings.
48.5 Temperature Controller Side Setting
48
49
Set value
50
51
Set value
52
53
Set value
54
Set value
55