Ethernet setting
Item
Description
The host is displayed. (The host is
Host
indicated with an asterisk (*).)
Set the network No. of the connected
N/W No.
Ethernet module.
(Default: blank)
Set the station No. of the connected
*1
Ethernet module.
PLC No.
(Default: blank)
Controller Type
AB(EtherNet/IP) (fixed)
Set the IP address of the connected
IP address
Ethernet module.
(Default: blank)
Port No.
44818 (fixed)
Communication
TCP (fixed)
Set the slot No. of the PLC to which the
Slot No.
Ethernet module is connected.
(Default: blank)
*1
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
54.3.2  Communication detail settings
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
(3) Setting IP address and port No
The same IP address cannot be set for the same
port No. The same IP address can be set for the
different port No.

54.3.3 PLC side setting

POINT
POINT
POINT
ALLEN-BRADLEY PLC
For details of ALLEN-BRADLEY PLCs, refer to the
following manuals.
Parameter setting
Set value
Set the following parameters with the software package
-
manufactured by the Allen-Bradley.
1 to 239
Item
Name
IP Address
1 to 64
Slot
AB(EtherNet/IP)
*1
(fixed)
PLC side IP
address
44818 (fixed)
TCP (fixed)
0 to 16
54. CONNECTION TO ALLEN-BRADLEY PLC
Manuals for ALLEN-BRADLEY PLCs
Settings
Sets the name.
IP address of the connected module
Slots No. for installing the EtherNet/IP communication module
For the IP address, make the same setting as that of each
Ethernet module set on GT Designer3.
Do not set the same IP Address as those of GOT and
controller on the Ethernet network.
For the address setting on GT Designer3, refer to the
following.
54.3.2  Communication detail settings
54.3 Ethernet Connection
48
49
50
*1
51
52
53
54
55
54 - 15