Ethernet Connection; System Configuration For Connecting To Fa-M3/M3V - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

50.3 Ethernet Connection

50.3.1 System configuration for connecting to FA-M3/M3V

PC link
FA-M3/M3V
FA-M3
module
PLC
Ethernet
interface
Model
*1
module
F3SP05
F3SP08
F3FP36
F3SP21
F3SP25
F3LE01-5T
F3SP35
• 10BASE-T
F3LE11-0T
F3SP28
Shielded twisted pair cable (STP)
F3LE12-0T
or
F3SP38
Unshielded twisted pair cable
F3SP53
(UTP):
F3SP58
Category 3, 4, and 5
F3SP59
F3SP76-7S
• 100BASE-TX
F3SP71-4S
F3LE11-0T
Shielded twisted pair cable (STP):
Category 5 and 5e
F3SP66
F3SP67
F3SP71-4N
-
F3SP76-7S
F3SP71-4S
*1
Product manufactured by Yokogawa Electric Corporation. For details of the product, contact Yokogawa Electric Corporation.
*2
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standard.
The use of shielded twisted pair cable (STP) is recommended in environments in which the performance against noise is
required.
*3
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*4
Use C or later version of GT11H-C-37P.
Connection cable
*2
Connection cable
Connector
conversion box
Cable model
GT16H-CNB-42S
GT16H-CNB-37S
GT16H-CNB-42S
GT16H-CNB-37S
Connector
conversion
box
External cable
GOT
*4
External cable
model
GT14H-C30-42P (3m)
GT14H-C60-42P (6m)
GT14H-C100-42P (10m)
GT11H-C30-37P (3m)
GT11H-C60-37P (6m)
GT11H-C100-37P (10m)
GT14H-C30-42P (3m)
GT14H-C60-42P (6m)
GT14H-C100-42P (10m)
GT11H-C30-37P (3m)
GT11H-C60-37P (6m)
GT11H-C100-37P (10m)
50. CONNECTION TO YOKOGAWA PLC
50.3 Ethernet Connection
Communication driver
Ethernet(
YOKOGAWA
), Gateway
GOT
Maximum
Number of connectable
segment
equipment
length
When PLC:GOT is N:1
The following shows the
number of PLCs for 1
GOT
TCP: 128 or less
UDP: 128 or less
*3
When PLC:GOT is 1:N
100m
The following shows the
number of GOTs for 1
PLC
TCP: 8 or less
UDP: 128 or less
(recommended to 16
units or less)
50 - 21
48
49
50
51
52
53
54
55

Advertisement