52.5.6 Connecting to DMC50
Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-D50/SLP-H21)of the
temperature controller.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
Communication mode
CPL
Data bit
8bits (fixed)
Parity bit
Even (fixed)
Stop bit
1bit (fixed)
*2*3*4
0 to F
Station address
*1
Adjust the settings with GOT settings.
*2
Set the station address using the rotary switch for the station
address.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of
other units.
Station address setting
Set the station address using the rotary switch for the
station address.
Rotary switch for the module address
52.5.7 Connecting to SDC45/46
Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-C45) of the temperature
controller.
Item
*1
9600bps ,19200bps, 38400bps
Transmission speed
*2
CPL
Communication mode
Data bit
7bits, 8bits
*1
Even, Odd, None
Parity bit
Stop bit
1bit, 2bits
Communication minimum
1 to 250ms
*5
response time
*3*4
0 to 120
Station address
*1
Adjust the settings with GOT settings.
*2
Set to CPL.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of
other units.
*5
When using the interface converter CMC10L, set the com-
munication minimum response time to 3ms or more.
52 - 40
52. CONNECTION TO AZBIL CONTROL EQUIPMENT
52.5 Control Equipment Side Setting
Set value
Set value
52.5.8 Connecting to CMS, CMF015
Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
*1
9600bps
Transmission speed
0: 8-bit data length, Even parity, Stop bit 1
Communication
condition selection
1: 8-bit data length, Non parity, Stop bit 2
*2*3
0 to 99
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
52.5.9 Connecting to CML, CMF050
Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
*1
9600bps
Transmission speed
00: 8-bit data length, Even parity, Stop bit 1
Communication condition
*1
selection
01: 8-bit data length, Non parity, Stop bit 2
*2*3
0 to 7F
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
52.5.10 Connecting to MQV
Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
*1
9600bps ,19200bps, 38400bps
Transmission speed
00: 8-bit data length, Even parity, Stop bit 1
Communication condition
*1
selection
01: 8-bit data length, Non parity, Stop bit 2
*2*3
0 to 127
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
Set value
Set value
Set value