25.5.8 Connecting to FREQROL-
F700/F700P
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
GOT connection
Parameters corresponding to inverter
destination
PU connector
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342
RS-485 terminal
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342, Pr.549
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit). Set Pr.160 (User group read selection) to 0 [The
simple mode and extended parameters can be
displayed] before making the parameter settings.
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled
Parameter No.
*1
Setting item
PU
RS-485
connector
terminal
PU communication
station number
/
Pr.117
Pr.331
RS-485 communication
station number
PU communication speed
/
Pr.118
Pr.332
RS-485 communication
*2
speed
PU communication stop
bit length*2
/
Pr.119
Pr.333
RS-485 communication
*2
stop bit length
PU communication parity
check
/
Pr.120
Pr.334
RS-485 communication
*2
parity check
Number of PU
communication retries
/
Pr.121
Pr.335
Number of RS-485
communication retries
PU communication check
time interval
/
Pr.122
Pr.336
RS-485 communication
check time interval
PU communication wait
time setting
/
Pr.123
Pr.337
RS-485 communication
wait time setting
PU communication CR/LF
selection
/
Pr.124
Pr.341
RS-485 communication
CR/LF selection
Protocol selection
-
Pr.549
Set value
Settings
0 to 31
25.5.13 Station
number setting
*4
19200bps
192
Data length: 7bit
10
Stop bit length: 1bit
1
Odd
The inverter will
9999
not come to an
alarm stop.
Communication
*4
9999
check suspension
0
0ms
With CR
*3
1
Without LF
Mitsubishi inverter
*3
0
protocol
25.5 FREQROL Series Inverter Side Settings
Parameter No.
*1
Setting item
PU
RS-485
connector
terminal
Operation mode selection
Pr.79
Link startup mode
Pr.340
selection
Communication
Pr.342
EEPROM write selection
*1
Setting items are parameter names described in the manual
of FREQROL-F700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is
required when the GOT is connected to the PU connector on
the inverter side.
HINT
HINT
HINT
Automatic setting with Pr.999 (FREQROL-F700P
series only)
If Pr.999 is set as the following, the communication
settings other than [PU communication station
number]
and
[Communication
selection] can be automatically set in a batch to the
default communication settings of the GOT side.
Parameter
Set
Description
No.
value
GOT initial settings
10
(PU connector)
*1
Pr.999
GOT initial settings
11
(RS-485 terminal)
*1
When the value of Pr.999 is monitored, 9999 is always
monitored.
25. INVERTER CONNECTION
Set value
Settings
PU
PU operation
1
connector
mode
External operation
RS-485
*3
0
mode at power on
PU
Refer to Pr.79
*3
connect
0
settings.
or
Network operation
RS-485
1
mode
Written to RAM
*3
0
and EEPROM
EEPROM
write
Operation in parameter setting
mode
[AUTO]
[GOT]
[1]
Write
-
25 - 39
25