51.4 GOT Side Settings
51.4.1
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YOKOGAWA
• Controller type: YOKOGAWA GREEN/UT100/
UT2000/UTAdvanced
• I/F: Interface to be used
• Driver: YOKOGAWA GREEN/UT100/UT2000/
UTAdvanced
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
51.4.2 Communication detail settings
OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
51 - 24
51. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
51.4 GOT Side Settings
Click!
[Controller Setting] from the
51.4.2 Communication detail settings
Item
Transmission
Speed
3.
Data Bit
Stop Bit
Parity
4.
Sum Check
Retry
Timeout Time
Host Address
Delay Time
Format
POINT
POINT
POINT
(1) Format
• When connecting to UT100 Series, specify the
format 1.
• When connecting to only GREEN/UT2000/
UTAdvanced Series, specifying the format 2 is
recommended.
(2) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
(3) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data length
used for communication with the connected
equipment. (Default: 8bit)
Specify the stop bit length for
communications. (Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
communication. (Default: Even)
Set whether or not to perform a sum check
during communication. (Default: None)
Set the number of retries to be performed
when a communication error occurs.
(Default: 0time)
Set the time period for a communication to
time out. (Default: 3sec)
Specify the host address (station No. of the
GOT to which the temperature controller is
connected) in the connected network.
(Default: 1)
Set this item to adjust the transmission
timing of the communication request from
the GOT. (Default: 5ms)
Select the communication format.
(Default: 1)
Format 1:
Accessible to GREEN/UT100/UT2000/UT
Advanced Series
Format 2:
Accessible to GREEN/UT2000/UT
Advanced Series, Not accessible to UT100
Series.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bit/8bit
1bit/2bits
None
Even
Odd
Done, None
0 to 5times
3 to 30sec
1 to 99
0 to 300ms
1/2