48.6 Device Range that Can Be Set
For details on the device range of controllers that can be used on GT14 Handy, refer to the following manuals.
GT Designer3 Version1 Screen Design Manual (Fundamentals)
GOT1000 Series Connection Manual (Non-Mitsubishi Products 2) for GT Works3
48.7 Precautions
Station number settings of temperature controller
In the system configuration, the temperature controller with the station number set with the host address must be
included. For details of host address setting, refer to the following.
48.4.2 Communication detail settings
FIX processing of temperature controller
The temperature controller power must not be turned off during the FIX processing. Otherwise, data within the non-
volatile memory will corrupt and the temperature controller will be unavailable.
GOT clock control
Since the temperature controller does not have a clock function, the settings of "time adjusting" or "time broad cast"
by GOT clock function will be disabled.
Cutting the portion of multiple connection of the controller
By setting GOT internal device, GOT can cut the portion of multiple connection of the controller. For example, faulty
station that has communication timeout can be cut from the system.
For details of the setting contents of GOT internal device, refer to the following manual.
GT Designer3 Version1 Screen Design Manual