Connecting to NP1L-RS1, NP1L-RS2,
NP1L-RS3, NP1L-RS4, NP1L-RS5
(1) Communication settings
Make the communication settings using setting
switches.
MODE switch
RS485 station
No. switch
RS485
terminator switch
Switch
MODE switch
MODE
RS485 station No.
Station No.
switch
RS485 terminator
Terminator
switch
*1
Set the MODE switch so that the communication port of the
general communication module to be connected to the GOT
operates as a loader.
*2
The switch is not used for connection with the GOT.
*3
Turn ON the terminating switch of the general
communication module which will be a terminal.
Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the
cable connection order. There is no problem even if
station numbers are not consecutive.
Station
Station
No.3
No.0
GOT
Examples of station number setting
(a) Direct specification
Specify the station No. of the PLC to be changed
when setting device.
Specification range
0 to 99
47 - 34
47. CONNECTION TO FUJI PLC
47.2 Serial Connection
Item
Set value
*1
1 to 3
*2
*3
Station
Station
Station
No.1
No.15
No.6