39.5 Indicating Controller Side Setting

POINT
POINT
POINT
(1) Shinko Technos indicating controller
For details of Shinko Technos indicating controller,
refer to the following manual.
User's Manual of the Shinko Technos indicating
controller
(2) Interface converter
For details on communication settings of the
RS232C/RS485 converter, refer to the following
manual.
User's Manual of RS232C/RS485 converter
Model
ACS-13A, DCL-33A, JC,
JCM-33A, JIR-301-M, PCD-300 Series,
PC-900 Series (PC-955-/M, C5, PC-
Indicating
935-/M, C5)
controller
FCD-100, FCR-100, FCR-23A,
FIR Series, PC-900 Series (PC-955-/
M, C, PC-935-/M, C)
Communication
IF-400
controller
39.5.1 Connecting to ACS-13A, DCL-
33A, JC, JCM-33A, JIR-301-
M, PCD-300 Series, PC-900
Series (PC-955-/M, C5, PC-
935-/M, C5)
Communication settings
Make the communication settings by operating the key
of the indicating controller.
Item
*1
9600bps, 19200bps
Transmission speed
Data Bit
7bits (Fixed)
Parity bit
Even (fixed)
Stop Bit
1bit (Fixed)
*2*3
0 to 95
Station No.
Communication protocol
Shinko protocol
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
*3
When setting the "95" to the station No., the read-out of data
cannot be performed.
39 - 10
39. CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER
39.5 Indicating Controller Side Setting
Refer to
39.5.1
39.5.2
39.5.3
Set value
39.5.2 Connecting to FCD-100, FCR-
100, FCR-23A, FIR Series,
PC-900 Series (PC-955-/M,
C, PC-935-/M, C)
Communication settings
Make the communication settings by operating the key
of the indicating controller.
Item
*1
9600bps, 19200bps
Transmission speed
Data Bit
7bits (Fixed)
Parity bit
Even (fixed)
Stop Bit
1bit (Fixed)
*1*2
0 to 95
Station No.
Communication protocol
Shinko protocol
*1
Adjust the settings with GOT settings.
*2
When setting the "95" to the station No., the read-out of data
cannot be performed.
39.5.3 Connecting to communication
converter (IF-400)
Communication settings
Make the communication settings using a setting
switch.
Item
*1
9600bps, 19200bps
Transmission speed
Sending/Receiving
1 character, 2 character
*2
switching period
*1
Adjust the settings with GOT and the indicating controller
settings.
*2
The setting of 1 character is recommended.
Set value
Set value