39.4 GOT Side Settings

39.4.1
Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Shinko Technos
• Controller Type: Shinko Technos Controller
• I/F: Interface to be used
• Driver: Shinko Technos Controller
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

39.4.2 Communication detail settings

OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
3.
4.
Click!
39. CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER
39.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data length
used for communication with the
Data Bit
connected equipment.
(Default: 7bit)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
Parity
communication.
(Default: Even)
Set the number of retries to be performed
Retry
when a communication error occurs.
(Default: 0time)
Set the time period for a communication
Timeout Time
to time out.
(Default: 3sec)
Specify the host address (station No. of
the GOT to which the indicating controller
Host Address
is connected) in the connected network.
(Default: 0)
Set this item to adjust the transmission
timing of the communication request from
Delay Time
the GOT.
(Default: 5ms)
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
39.4 GOT Side Settings
32
33
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bit/8bit
34
1bit/2bits
None
Even
Odd
35
0 to 5times
3 to 30sec
0 to 94
36
0 to 300ms
37
38
39
39 - 9