Mitsubishi Electric GT14 User Manual page 520

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

Switch setting of peripheral connection
module
Set the station number setting switch, data link
transmission speed setting switch, and operation setting
DIP switch.
(1) Station number setting switch
Station number setting
Description
switch
AJ65BT-R2N
station number
setting
: Necessary
(2) Data link transmission speed setting switch
Data link transmission
Description
speed setting switch
Data link
transmission
speed setting
: Necessary
(3) Mode setting switch
Mode setting switch
Description
Mode setting
switch
: Necessary
24 - 12
24. CC-Link CONNECTION (Via G4)
24.5 PLC Side Setting
(3)
(2)
(1)
2
4
(4)
Setting necessity at
Set value
GOT connection
1 to 64
: As necessary
: Not necessary
Setting necessity at
Set value
GOT connection
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
: As necessary
: Not necessary
Setting necessity at
Set value
GOT connection
5 (fixed)
(MELSOFT/
connection
mode)
: As necessary
: Not necessary
(4) RS-232 transmission setting switch
RS-232 transmission
Setting
setting switch
switch
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
: Necessary
*1
The peripheral connection module operates at the
transmission speed set on the GOT.
24.5.6 [Controller Setting] of GT Designer3
POINT
POINT
POINT
Precautions
when
module
(1) Operation mode setting switch
Be sure to set the Operation mode setting switch
to "5" (MELSOFT/connection mode).
(2) RS-232 transmission setting switch
Turn OFF SW1 through SW8 of the RS-232
transmission setting switch.
If any switch of SW1 through SW8 is ON, a setting
error will occur (RUN LED turns off).
Setting
Set
necessity at
Description
value
GOT
connection
Peripheral
OFF
transmission
(fixed)
*1
speed
Date bit
OFF
length
(fixed)
Parity bit
OFF
setting
(fixed)
Stop bit
OFF
length
(fixed)
: As necessary
: Not necessary
setting
peripheral
connection

Advertisement

Table of Contents
loading

Table of Contents