29.3.2 RS-422 cable
Connection diagram
RS422 connection diagram 1)
GOT side
SDA
1
RDA
2
RSA
3
CSA
4
SG
5
SDB
6
RDB
7
RSB
8
CSB
9
RS422 connection diagram 2)
External cable
GT11H-C-37P side
FG(Shield)
1
SDA
2
SDB
3
RSA
4
RSB
5
RDA
6
RDB
7
CSA
8
CSB
9
SG
10
RS422 connection diagram 3)
External cable
GT11H-C-37P side
FG(Shield)
Shield
SDA
W/R (A)
SDB
W/BK (A)
RSA
GY/R (A)
RSB
GY/BK (A)
RDA
O/R (A)
RDB
O/BK (A)
CSA
Y/R (A)
CSB
Y/BK (A)
SG
PK/R (A)
29 - 6
29. MULTIPLE GOT CONNECTION FUNCTION
29.3 Connection Diagram
(1) Cable length
(2) Connector conversion box side connector
GOT side
RDA
2
SDA
1
CSA
(3) External cable side connector
4
RSA
3
SG
5
RDB
7
SDB
6
CSB
9
RSB
8
GT14 Handy side
-
-
RDA
2
RDB
7
CSA
4
CSB
9
SDA
1
SDB
6
RSA
3
RSB
8
SG
5
GT14 Handy side
-
-
RDA
2
RDB
7
CSA
4
CSB
9
SDA
1
SDB
6
RSA
3
RSB
8
SG
5
Precautions when preparing a cable
The length of the RS-422 cable must be 30m or less.
For the connector conversion box side connector, refer
to the following.
6.6 Connector Conversion Box
For the connector specifications of the external cable
side, refer to the following.
8.2 External Cable, Relay Cable