Got Side Settings - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

25.4 GOT Side Settings

25.4.1
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver: FREQROL 500/700/800, SENSORLESS
SERVO
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
25.4.2 Communication detail settings
OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
25 - 34
25. INVERTER CONNECTION
25.4 GOT Side Settings
Click!
[Controller Setting] from the
25.4.2
Make the settings according to the usage environment.
Item
Transmission
Speed
3.
Data Bit
4.
Stop Bit
Parity
Retry
Timeout Time
Delay Time
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be changed
on the Utility's [Communication setting] after
writing [Communication Settings] of project data.
For details on the Utility, refer to the following
manual.
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
HINT
HINT
HINT
Cutting the portion of multiple connection of the controller
By setting GOT internal device, GOT can cut the
portion of multiple connection of the controller. For
example, faulty station that has communication
timeout can be cut from the system.
For details of the setting contents of GOT internal
device, refer to the following manual.
Communication detail settings
Description
Set this item when change the
transmission speed used for
communication with the
connected equipment.
(Default: 19200bps)
Set this item when change the
data length used for
communication with the
connected equipment.
(Default: 7bits)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform
a parity check, and how it is
performed during communication.
(Default: Odd)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
Set the time period for a
communication to time out.
(Default: 3sec)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 10ms)
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
GT Designer3 Version1 Screen Design Manual
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
1 to 30sec
0 to 300ms

Advertisement