23.4.14 Connecting to CC-Link IE Field
Network Ethernet adapter
module
This section describes the settings of the GOT, the
Ethernet adapter module, and PLC side in the following
system configuration.
System configuration
<GOT>
(Use default value for settings other than the following.)
Network No.
PC No.
IP address
Port No.
Communication
format
Ethernet
<Ethernet adapter module>
(Use default value for settings other than the following.)
Ethernet setting
IP address
CC-Link IE Field Network setting
Network No.
Station No.
CC-Link IE Field Network
HUB
<CC-Link IE Field Network master/local module>
(Use default value for settings other than the following.)
Network Type
: CC IE Field (Master station)
Network No.
: 1
PC No.
: 0
Total Stations
: 2
<CC-Link IE Field Network master/local module>
(Use default value for settings other than the following.)
Network Type
: CC IE Field (Local station)
Network No.
: 1
PC No.
: 2
*1
Set the GOT network No. according to the third octet
(network No.) of the Ethernet adapter module IP address.
*2
The CC-Link IE field network master/local module is mounted
on slot 0 of the base unit.
The start I/O No. of the CC-Link IE field network master/local
module is set at [0].
*1
:3
:1
:192.168.3.18
:5001
:UDP (fixed)
:192.168.3.30
:1
:1
*2
*2
GX Works2 network parameter Ethernet/CC
IE/MELSECNET
For detailed settings on the PLC side, refer to the
following manual.
MELSEC-Q CC-Link IE Field Network Master/
Local Module User's Manual
(1) Setting of Network Type, Network No., and total
stations
Example: Master station setting
Item
Master station
CC IE Field
Network Type
(Master Station)
Network No.
Total Stations
Station No.
(2) Routing parameter setting
Set the followings as necessary.
Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number cannot be
set twice or more (multiple times).
Therefore, the one that can access to other station from
the request source host GOT is 64 kinds of [Transfer
Network No.]s.
Item
Target Network No.
Relay Network No.
Relay Station No.
23. ETHERNET CONNECTION
23.4 PLC Side Setting
Set value
Local station
CC IE Field
(Local Station)
1
1
2
-
0 (fixed)
2
Range
1 to 239
1 to 239
1 to 64
23 - 51
17
18
19
20
21
22
23
24