(3) Routing setting
Up to 238 [Target Station Network No.] scan be set.
However, the same target station network number
cannot be set twice or more (multiple times).
Therefore, the one that can access to other station from
the request source host GOT is 238 kinds of [Target
Station Network No.]s.
Item
Target Station network No.
Relay Station network No.
Relay station No.
POINT
POINT
POINT
Routing parameter setting of request source
Routing parameter setting is also necessary for the
request source GOT.
For the setting, refer to the following.
23.3.4 Routing parameter setting
(4) Communication confirmation
The INIT. LED on the Ethernet module turns on when
the module is ready to communicate.
For confirming the communication state, refer to the
following.
 Confirming the communication state of
Ethernet module
RJ71EN71
RUN
ERR.
INIT.
COM.ERR.
OPEN
100M
SD
RD
Range
1 to 239
1 to 239
1 to 120
[Controller Setting] and [Ethernet] of GT
Designer3
(1) Controller setting
Item
GOT NET No.
GOT PLC No.
GOT IP Address
GOT Port No.
(Communication)
GOT Port No.
(Ethernet Download)
Default Gateway
Subnet Mask
Retry
Startup Time
Timeout Time
Delay Time
(2) Ethernet setting
Item
Host
N/W No.
PLC No.
Ethernet
Type
setting No.1
IP address
Port No.
Communication
POINT
POINT
POINT
[Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT Designer3,
refer to the following.
23.3.1 Setting communication interface
(Communication settings)
23. ETHERNET CONNECTION
23.4 PLC Side Setting
Set value (Use default value)
1
1
192.168.3.18
5001
5014
0.0.0.0
255.255.255.0
3times
3sec
3sec
0ms
Set value
*
1
2
RJ71EN71
192.168.3.19
5001 (fixed)
UDP (fixed)
23 - 23
17
18
19
20
21
22
23
24