25.5.12 Connecting to MD-CX522-
K(-A0)
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
GOT connection
Parameters corresponding to inverter
destination
PU connector
(2) Communication settings of inverter
• Set the following parameters using the PU
(parameter unit).
• After setting the parameters for the
communication settings, reset the inverter.
• Do not change these parameters, even though
they can be monitored from the GOT. If they are
changed, communication with the GOT is
disabled
Parameter
*1
Setting item
No.
Station No.
Pr.117
Communication
Pr.118
*2
speed
Stop bit length/data
Pr.119
*2
length
Parity check
Pr.120
*2
presence/absence
Number of
communication
Pr.121
retries
Communication
Pr.122
check time interval
Wait time setting
Pr.123
CR/LF presence/
Pr.124
absence selection
*1
Setting items are parameter names described in the manual
of MELIPM series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
Pr.79, Pr.117 to Pr.124
Set
Settings
value
25.5.13Station
0 to 31
number setting
*3
19200bps
192
Data length: 7bit
10
Stop bit length: 1bit
1
Odd
The inverter will not come
9999
to an alarm stop.
Communication check
9999
suspension
0
0ms
*3
With CR, without LF
1
25.5.13 Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
Station
Station
Station
Station
No.3
No.3
No.0
No.0
GOT
Examples of station number setting
(1) Direct specification
When setting the device, specify the station number of
the inverter of which data is to be changed.
(2) Indirect specification
When setting the device, indirectly specify the station
number of the inverter of which data is to be changed
using the 16-bit GOT internal data register (GD10 to
GD25).
When specifying the station No. from 100 to 155 on GT
Designer3, the value of GD10 to GD25 compatible to
the station No. specification will be the station No. of
the inverter.
Specification
Compatible
station No.
device
100
GD10
101
GD11
102
GD12
103
GD13
104
GD14
105
GD15
106
GD16
107
GD17
108
GD18
109
GD19
110
GD20
111
GD21
112
GD22
113
GD23
114
GD24
115
GD25
25. INVERTER CONNECTION
25.5 FREQROL Series Inverter Side Settings
Station
Station
Station
Station
Station
Station
No.1
No.1
No.21
No.21
No.6
No.6
Specification
range
0 to 31
Setting range
0 to 31
For the setting other than the above, an
error (dedicated device is out of range)
will occur.
25 - 43
25
26
27
28
29
30
31