Connecting To Sdc20/21, Sdc30/31; Connecting To Cmc10L - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

52.5.4 Connecting to SDC20/21,
SDC30/31
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps
Transmission speed
Data bit
8bits
Parity bit
Disable
Stop bit
2bits
*2*3
0 to 127
Station address
*1
Set the same transmission speed as that of the GOT side.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.

52.5.5 Connecting to CMC10L

Communication settings
Make the communication settings by operating the DIP
switch of the control equipment.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
*2
Frame length
*1
Set the same transmission speed as that of the GOT side.
*2
The sum of data length, parity bit and stop bit
Settings by switch
Front view of CMC10L body
Set value
Set value
9 to 15bits
DIP switch
Mode selector
switch
Rear view of CMC10L body
52. CONNECTION TO AZBIL CONTROL EQUIPMENT
(1) Setting DIP switches
(a) Transmission speed settings
Switch No.
Transmission
speed (bps)
1
2
3
9600
ON
OFF
ON
19200
OFF
ON
ON
38400
ON
ON
ON
(b) Frame length settings
Switch No.
Frame length
4
5
6
8bits
OFF
OFF
OFF
9bits
ON
OFF
OFF
10bits
OFF
ON
OFF
11bits
ON
ON
OFF
12bits
OFF
OFF
ON
13bits
ON
OFF
ON
14bits
OFF
ON
ON
15bits
ON
ON
ON
(c) Connecting terminating resistors
Switch No.
Terminating
resistor
8
Enable
ON
Disable
OFF
(2) Mode selector switch settings
Set the switch to "TERMINAL".
52.5 Control Equipment Side Setting
Set these
switches
Set these
switches
Set these
switches
52 - 39
48
49
50
51
52
53
54
55