GOT installation status check sheet
Check the current installation status of the GOT you are using against the GOT installation status described in the
upper column of items (1) to (7).
When the measure described in the lower column is needed, take the measure for the current status.
When the measure is taken, check the result, "Effective" or "Ineffective".
(1) Panel inside wiring
Current status
Measure for the
cables mixed
(2) Panel outside wiring
Current status
Communication cable
Power line
Fig.
A
Measure for
the cables
installed
together
Fig.
100mm or more
B
NFB
MC
MC
RA
RA
NFB
MC
MC
RA
RA
Power line
Communication cable
Wiring
Separator
Power
duct
line
Signal
Power
Communication
line
line
cable
The power line connected to the power or
servo amplifier and the communication
cable are mixed in the duct.
Wiring the power line and communication
cable in the panel without mixing them in
the duct can reduce the influence of noise.
The power line and communication cable
are installed together.
Leading the power line and
communication cable outside the panel
at separate places can make the
communication cable less influenced by
noise from the power line. Installing the
communication cable apart from the
power line or using a separator (made of
metal) in the duct as shown in Fig. B can
make the communication cable less
influenced by noise.
20. TROUBLESHOOTING
20.1 GOT Restoration Sheet
17
18
Mixed
Not mixed
19
20
Effective
Ineffective
21
Installed together
Not installed
together
22
Effective
Ineffective
23
24
20 - 5