(2) Precautions when preparing a cable
(a) Cable length
The total distance (between GOT and controllers)
of RS-422 cable must be 13m or less.
(b) Connector conversion box side connector
For the connector conversion box side connector,
refer to the following.
6.6 Connector Conversion Box
(c) External cable side connector
For the connector specifications of the external
cable side, refer to the following.
8.2 External Cable, Relay Cable
(d) TOSHIBA PLC side connector
Use the connector compatible with the TOSHIBA
PLC.
For details, refer to the TOSHIBA PLC user's
manual.
(3) Connecting terminating resistors
(a) TOSHIBA PLC side
When connecting a TOSHIBA PLC to a GOT, a
terminating resistor must be set to the TOSHIBA
PLC.
For the setting of the terminating resistor, refer to
the following manual.
TOSHIBA PLC user's Manual
• T2 (PU224), T2N, T3, T3H, model 3000 (S3)
Connect the terminating resistor (1/2W-120Ω)
across RXA and RXB.
• T2E, model 2000 (S2, S2T, S2E)
Short across the RXA and TERM terminals.
41. CONNECTION TO TOSHIBA PLC
41.2 Serial Connection
40
41
42
43
44
45
46
47
41 - 9