When the FA transparent function is used in
an Ethernet connection
(1) GX Developer function or GX Works2 function
When the FA transparent function is used in an
Ethernet connection, the following GX Developer
functions or GX Works2 functions cannot be executed.
The message [The executed function is not supported.
Please check the manual and other documentation.] is
displayed on GX Developer.
Unsupported functions
• Remote Reset
• Remote system reset
• Remote RUN
• Remote STOP
• Remote PAUSE
• Remote STEP-RUN
• Remote latch clear
• Write clock data
• Clear malfunction log
• Remote password function
• CC-Link IE controller
• Network diagnostics
• Ethernet diagnostics
(PING test/loopback test with the
Ethernet module (Q series))
(2) GOT station monitoring function
When the FA transparent function is used in an
Ethernet connection, GOT station monitoring function
cannot be operated.
Therefore, in the cases of [no connection target], [PLC
power OFF], etc., the monitoring of the GOT delays for
the timeout time.
Remark
-
Inexecutable only when
specify all stations/groups
has been performed.
31.7.2 When using GX Works3, GX
Works2, GX Developer
When connecting to QCPU (A mode)
When connecting to QCPU (A mode), set the PLC type
to "A4UCPU" or "QCPU (A mode)" on GX Developer.
When [monitor conditions] have been set on
GX Works3, GX Works2, GX Developer
(1) Monitoring performance of the GOT is temporarily
suspended.
(2) The GOT cannot respond to the touch switch operation
and numerical/ASCII inputs.
(3) Writing to PLC results in a system alarm occurrence
and displays the message, "315 Device writing error.
Correct device.".
(4) While setting the monitor conditions, do not perform
any operation which makes the GOT restart (e.g.
downloading project data, changing utility data).
Doing so may display a system alarm, "402
Communication timeout. Confirm communication
pathway or modules." when the GOT restarts.
When the monitor conditions setting for the PLC CPU
has not been canceled, reconnect GX Works3, GX
Works2, GX Developer to cancel the setting. (An error
may be output when the monitor conditions setting is
canceled.)
(5) When the time check of GX Works3, GX Works2, GX
Developer is set to 30 seconds or more in the monitor
condition settings, the message "402 Communication
timeout. Confirm communication pathway or modules."
may appear.
Set the time check time of GX Works3, GX Works2, GX
Developer to 30 seconds or less.
When exiting GX Works3, GX Works2, GX
Developer
For 45 seconds after GX Works3, GX Works2, GX
Developer have been exited, the GOT continues
monitoring at the same speed as when the FA
transparent function is working.
31. FA TRANSPARENT FUNCTION
31.7 Precautions
25
26
27
28
29
30
31
31 - 49