Ethernet Connection; System Configuration For Connecting To Mp-920 Or Mp2200 Or Mp2300 Or Mp2300S Or Cp-9200Sh Or Cp-312 Or Cp-317 - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

49.3 Ethernet Connection

49.3.1
System configuration for connecting to MP-920 or MP2200 or MP2300 or
MP2300S or CP-9200SH or CP-312 or CP-317
MP920, MP2200,
Communications
MP2300, CP-9200SH,
Module
CP-312, CP-317
PLC
Communication
Model
*3
Connection diagram number
module
MP-920
218IF
MP2200
• 10BASE-T
218IF-01
MP2300
Shielded twisted pair cable (STP)
218IF-02
MP2300S
or
Unshielded twisted pair cable
(UTP): Category 3, 4, and 5
• 100BASE-TX
CP-9200SH
Shielded twisted pair cable
CP-218IF
CP-312
(STP): Category 5 and 5e
CP-317
218TXB
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standard.
The use of shielded twisted pair cable (STP) is recommended in environments in which the performance against noise is
required.
*2
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*3
Product manufactured by YASKAWA Electric Corporation. For details of the product, contact YASKAWA Electric Corporation.
*4
Use C or later version of GT11H-C-37P.
Connection cable
*1
Connection cable
Connector
Cable model
conversion box
GT16H-CNB-42S
GT16H-CNB-37S
GT16H-CNB-42S
GT16H-CNB-37S
GT16H-CNB-42S
GT16H-CNB-37S
GT16H-CNB-42S
GT16H-CNB-37S
Connector
conversion
box
External cable
Maximum
GOT
*4
segment
External cable
model
length
GT14H-C30-42P (3m)
GT14H-C60-42P (6m)
GT14H-C100-42P (10m)
GT11H-C30-37P (3m)
GT11H-C60-37P (6m)
GT11H-C100-37P (10m)
GT14H-C30-42P (3m)
GT14H-C60-42P (6m)
GT14H-C100-42P (10m)
GT11H-C30-37P (3m)
GT11H-C60-37P (6m)
GT11H-C100-37P (10m)
100m
GT14H-C30-42P (3m)
GT14H-C60-42P (6m)
GT14H-C100-42P (10m)
GT11H-C30-37P (3m)
GT11H-C60-37P (6m)
GT11H-C100-37P (10m)
GT14H-C30-42P (3m)
GT14H-C60-42P (6m)
GT14H-C100-42P (10m)
GT11H-C30-37P (3m)
GT11H-C60-37P (6m)
GT11H-C100-37P (10m)
49. CONNECTION TO YASKAWA PLC
49.3 Ethernet Connection
Communication driver
Ethernet(
), Gateway
YASKAWA
GOT
Number of connectable equipment
When PLC (module): GOT is N:1
The following shows the number
of PLCs for 1 GOT
TCP: 128 or less
UDP: 128 or less
*2
When PLC (module): GOT is 1:N
The following shows the number
of GOTs for 1 PLC (module)
TCP/UDP: 10 or less
49 - 23
48
49
50
51
52
53
54
55