Error
Error message
code
File system error occurred in
356
PLC.
Confirm file register.
Error in specified PLC drive
357
Confirm PLC drive.
PLC file access failure.
358
Confirm PLC drive.
Processing from another
359
peripheral device.
Execute it after.
0 divisor division error.
360
Confirm operation expression.
Specified device No. is out of
361
range.
Invalid device value in time
362
action setting
Upper and lower limit value error.
370
Confirm value setting.
Insufficient USB drive capacity.
380
Confirm the drive capacity.
USB drive is not installed or in a
381
removable state.
382 USB drive is not formatted.
Unable to overwrite. USB drive is
383
write-protected.
USB drive error. Replace USB
384
drive.
Error occurred in the specified file register when executing the recipe
function by specifying the file register name.
• Execute the recipe function again after confirming the file register
name.
• Execute the recipe function again after formatting the PC memory in
the specified PLC CPU drive with GX Developer.
When executing the recipe function specifying the file register name,
error occurred in PLC CPU drive.
• Execute the recipe function again after confirming the specified PLC
CPU drive.
• Execute the recipe function again after formatting the PC memory in
the specified PLC CPU drive with GX Developer.
When the recipe function is executed specifying the file register name,
PLC CPU file register could not be accessed.
• Execute the recipe function again after confirming the specified PLC
CPU drive / file register name. (When you specify drive 0, execute the
recipe function again after changing to other drives.)
• Confirm whether the SD card or USB memory are write-protected, and
execute the recipe function again.
When the recipe function is executed specifying the file register name,
other peripherals carry out the process to the file register.
Wait until the processing of other peripherals end, and execute the recipe
function again.
Zero division occurred by the data operational expression.
Review the data operational expression so that the divisor should not
become 0.
The entered file number is out of range.
Check the entered file number, and enter a valid value (1 to 9999).
When controllers are controlled with the GOT's time action function, the
set No. is our of range, or the set device values regarding the operation
settings are out of range or invalid.
Set valid values.
The setting of lower/upper limit value is [Upper limit < Lower limit].
Correct the setting so as to be "Upper limit &inequalityLEM Lower limit".
Available memory of the USB memory is insufficient.
Confirm the available memory of the USB memory, and increase the
memory if it is low.
If the USB memory is not installed, install it.
If the USB memory is ready to be removed, install it again.
Memory card is not formatted or in a format not conformed by a GOT.
Reformat the USB memory.
USB memory is write-protected.
Cancel the write-protection of USB memory.
USB memory is faulty.
Replace the USB memory.
20.2 Error Message and System Alarm