Got Side Settings; Setting Communication Interface (Communication Settings); Communication Detail Settings - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

44.4 GOT Side Settings

44.4.1
Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Panasonic
• Controller Type: Panasonic MEWNET-FP
• I/F: Interface to be used
• Driver: Panasonic MEWNET-FP
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

44.4.2 Communication detail settings

OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
3.
4.
Click!
44. CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC
44.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data length
used for communication with the
Data Bit
connected equipment.
(Default: 8bit)
Set the number of retries to be performed
when a communication timeout occurs.
Retry
When receiving no response after retries,
the communication times out.
(Default: 0time)
Set the time period for a communication
Timeout Time
to time out.
(Default: 3sec)
Specify the host address (station No. of
the PLC to which the GOT is connected)
Host Address
in the network of the GOT.
(Default: 1)
Set this item to adjust the transmission
timing of the communication request from
Delay Time
the GOT.
(Default: 0ms)
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
44.4 GOT Side Settings
40
41
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
42
7bit/8bit
0 to 5times
43
3 to 30sec
1 to 31
44
0 to 300
(ms)
45
46
47
44 - 29