50.2.8 Connecting to PC link module
(F3LC01-1N, F3LC11-1N,
F3LC11-2N, F3LC11-2F)
Switch setting on the PC link module
Set the switches accordingly.
POINT
POINT
POINT
Switch setting
Set the switches before mounting the Ethernet
Interface Module on the base unit.
F3LC01-1N
F3LC11-2N
F3LC11-1N
F3LC11-2F
TERMINATOR
2-
4-WIRE
OFF
SD A
SD B
RD A
A
SD B
SG
SHIELD
(1) Transmission speed setting switch
Set the same transmission speed of the GOT.
*1
Setting
4
5
6
*1
Only transmission speeds available on the GOT side are
shown.
50 - 16
50. CONNECTION TO YOKOGAWA PLC
50.2 Serial Connection
STATION
NO.
(3)
Side view indicated by A
(For the F3LC01-1N,
F3LC11-1N, F3LC11-2N)
(4)
With right side cover
removed
A
O
1
2
F
3
F
4
5
6
7
8
Side view indicated by A
(For the F3LC11-2F)
With right side cover
removed
O
1
O
1
2
2
F
F
3
3
F
F
4
4
5
5
6
6
7
7
8
8
(5)
Transmission speed
4800bps
9600bps
19200bps
(2) Data format setting switch
Set the data length, parity, stop bit and checksum
consistent with the corresponding settings on the GOT
side.
(3) Station No. switch (F3LC11-2N only)
(1)
(2)
(4) Terminator switch (F3LC11-2N only)
(1)
(5) SW3 switch (F3LC11-2F only)
Unused switch.Turn off all the unused switches.
(2)
Switch No.
Description
1
Data bit
2
Parity
3
4
Stop bit
5
Checksum
End character
6
specification
7
Protect function
8
-
Rotary
Description
switch
1)
Station No. (10's digit)
2)
Station No. (1's digit)
Setting
Description
4-WIRE
Resistor connected (4-wire type)
Setting
ON (8bits),
OFF (7bits)
ON (done),
OFF (none)
ON (even),
OFF (odd)
ON (2bits),
OFF (1bit)
ON (done),
OFF (none)
OFF (none)
OFF (none)
OFF
Setting