• Transmission speed setting (SW05 to SW07)
Set the transmission speed (SW05 to SW07) as
follows.
The transmission speed setting must be consistent
with that of the GOT side.
Setting switch
4800bps
SW05
OFF
SW06
OFF
SW07
ON
*1
Only transmission speeds available on the GOT side are
shown.
(d) A1SCPUC24-R2
Transmission
Setting
specifications
switch
setting switch
Write during RUN
1
enabled/disabled
setting
2
Transmission speed
3
setting
4
5
Data bit setting
6
Parity bit setting
Even/odd parity
7
setting
8
Stop bit setting
9
Sum check setting
• Transmission speed setting (2 to 4)
Set the transmission speed (2 to 4) as follows.
The transmission speed setting must be consistent
with that of the GOT side.
Setting switch
4800bps
2
OFF
3
OFF
4
ON
*2
Only transmission speeds available on the GOT side are
shown.
22 - 32
22. COMPUTER LINK CONNECTION
22.5 PLC Side Setting
*1
Transmission speed
9600bps
19200bps
ON
OFF
OFF
ON
ON
ON
Description
Set value
Enabled
ON
(Consistent
See
with the GOT
description
side
s below.
specifications.)
8bits
ON
Set
ON
Odd
OFF
1bit
OFF
Set
ON
*2
Transmission speed
9600bps
19200bps
ON
OFF
OFF
ON
ON
ON
(e) A2CCPUC24, A2CCPUC24-PRF
Transmission
Setting
specifications
switch
setting switch
SW11
Transmission speed
SW12
setting
SW13
SW14
Data bit setting
SW15
Parity bit setting
Even/odd parity
SW16
setting
SW17
Stop bit setting
SW18
Sum check setting
SW19
Main channel setting
Write during RUN
SW20
enabled/disabled
setting
• Transmission speed setting (SW11 to SW13)
Set the transmission speed (SW11 to SW13) as
follows.
The transmission speed setting must be consistent
with that of the GOT side.
Setting switch
4800bps
SW11
OFF
SW12
OFF
SW13
ON
*1
Only transmission speeds available on the GOT side are
shown.
(3) Station number setting switch
*2
Station number switch
Set the station number of the
computer link module to
which an access is made
from the GOT.
*2
The station number setting switch in the figure is for the
A1SJ71UC24-R4.
POINT
POINT
POINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
Set
Description
value
(Consistent
See
with the GOT
descriptio
side
ns below.
specifications.)
8bits
ON
Set
ON
Odd
OFF
1bit
OFF
Set
ON
RS-232
OFF
Enabled
ON
*1
Transmission speed
9600bps
19200bps
ON
OFF
OFF
ON
ON
ON
Description